  The MTL5546Y-T accepts a 4/20mA floating signal from a safe-area controller to drive a current/pressure converter (or any other load up to 800Ω) in a hazardous area. For HART valve positioners, the module also permits bi-directional transmission of digital communication signals. Process controllers with a readback facility can detect open circuit in the field wiring: if this occurs, the current taken into the terminals drops to a preset level.

image.png

  SPECIFICATION

  See also common specification

  Number of channels

  One

  Location of I/P converter

  Zone 0, IIC, T4–6 hazardous area if suitably certified

  Div. 1, Group A, hazardous location

  Working range

  4 to 20mA

  Digital signal bandwidth

  500Hz to 10kHz

  Maximum load resistance

  800Ω (16V at 20mA)

  Output resistance

  > 1MΩ

  Under/over range capability

  Under range = 1mA

  Over range = 24mA (load ≤ 520Ω)

  Input and output circuit ripple

  < 40µA peak-to-peak

  Transfer accuracy at 20°C

  Better than 20µA

  Temperature drift

  < 1.0µA/°C

  Input characteristics

image.png

  Response time

  Settles within 200µA of final value within 100ms

  Communications supported

  HART

  LED indicator

  Green: power indication

  Maximum current consumption (with 20mA signals into 250Ω load)

  35mA at 24V dc

  Power dissipation within unit (with 20mA signals into 250Ω load)

  0.8W at 24V

  Operating temperature range

  -20°C to + 65°C (-6 to + 149°F)

  Safety description

  Uo=28V Io=93mA Po=651mW Um = 253V rms or dc