  The MTL4549C/MTL4549Y/MTL5549Y accepts 4/20mA floating signals from safe-area controllers to drive 2 current/pressure converters (or any other load up to 800Ω) in a hazardous area. For HART valve positioners, the module also permits bi-directional transmission of digital communication signals. Process controllers with a readback facility can detect open or short circuits in the field wiring: if these occur, the current taken into the terminals drops to a preset level. The MTL4549C and MTLx549Y are very similar to the MTLx549 except that they provide open circuit detection only (i.e. no short-circuit detection).

image.png

  SPECIFICATION

  See also common specification

  Number of channels

  Two

  Location of I/P converter

  Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A, hazardous location

  Working range

  4 to 20mA

  Digital signal bandwidth

  500Hz to 10kHz

  Maximum load resistance

  800Ω (16V at 20mA)

  Minimum load resistance

  90Ω (short-circuit detection at < 50Ω)

  Output resistance

  > 1MΩ

  Under/over range capability

  Under range = 1mA

  Over range = 24mA (load ≤ 520Ω)

  Input and output circuit ripple

  <40µA peak-to-peak

  Communications supported HART

  Transfer accuracy at 20°C

  Better than 20µA

  Temperature drift

  < 1.0µA/°C

  Response time

  Settles within 200µA of final value within 100ms

  LED indicator

  Green: power indication

  Maximum current consumption (with 20mA signals into 250Ω load)

  70mA at 24V dc

  Power dissipation within unit (with 20mA signals into 250Ω load)

  1.6W at 24V

  Safety description (each channel)

  Uo=28V Io=93mA Po=0.65W Um = 253V rms or dc